Reducing Motor Insulation Stress When Using Variable Frequency Drives

A variable frequency drive (VFD), sometimes known as a variable speed drive, is used to control AC induction motor speed and torque by varying the motor input frequency and voltage. VFDs improve control, increase efficiency, and extend the motor’s operating life by reducing mechanical and thermal stresses. However, VFDs may also lead to degradation of the coils that produce the magnetic field in the motor’s stator and their insulation.

Motors Fail for Many Reasons

Motors may fail for many reasons unrelated to the VFD itself. The motor’s stator windings may overheat and burn out due to insufficient cooling of the motor, an overload, improper wiring, incorrect motor data supplied to the VFD, or running the motor for an extended time at low speed in a constant torque application. In other cases, loose wire strands in the motor’s conduit box, nicked insulation in the motor cables, or moisture in the motor or in the conduit between the VFD and the motor can result in a malfunction. And sometimes, the insulation in the motor’s windings may breakdown due to the interaction between the VFD and the motor’s stator windings.

VFD-Induced Motor Insulation Breakdown

An AC induction motor’s stator coils possess an electrical property called “inductive reactance,” that produces a back-voltage that opposes changes in current flow. Gradual changes in current flow are typically unproblematic. However, when a fast-rising voltage pulse is applied, the back-voltage generated by the motor’s coils can cause a voltage spike. This overshoot interacts with the inductance and capacitance of the motor and cables, causing the voltage to oscillate. If the peak voltage generated by this oscillation escalates too high, it can break through the motor’s insulation and cause the motor’s windings to short.

Measuring the PWM Pulse

The Pulse Width Modulation (PWM) digital signal can be measured in a number of ways. The peak voltage, or Vpeak, indicates the amount of stress imposed on the motor’s stator insulation. The rise time of the pulse, typically defined as the time required for the pulse to rise from 10% to 90% of its peak voltage, is also assessed—the shorter the rise time, the greater the stress on the motor’s insulation. A third measurement is dV/dt, the rate of the rise of the pulse’s voltage, calculated by dividing the change in voltage (dV) by the change in time (dt). As the rise time shortens, the dV/dt value becomes larger, placing added stress on the motor’s insulation.

Choosing the Right Motor

The National Electrical Manufacturers Association (NEMA) set the standard for how high a voltage the insulation in a general-purpose motor should safely be able to withstand. For a base voltage rating of up to 600 V, they selected a value of 1000 V. However, since the voltage pulse that a PWM VFD applies to a motor may overshoot the DC bus voltage that generated the pulse, NEMA created a new standard to ensure that these motors had sufficient stator insulation to ensure reliable operation when used with VFDs. The 1993 version of NEMA MG 1, Part 31 states that a definite-purpose motor for use with a VFD should have stator windings that can withstand 1600 V. A general-purpose motor may be used for an application if voltage overshoot doesn’t exceed 1000 V. Some factors that affect voltage overshoot include the rise time of the VFD’s PWM pulses, the length of the power cables between the VFD and the motor, power line voltage, load on the motor, PWM switching frequency, and the size of the motor.

Choosing the right VFD and motor for your unique application can be challenging. That’s why the experts at Advanced Industrial Devices deliver practical, efficient, ingenious and empowering solutions to ensure customer success. To find out more about AID’s engineered solutions and capabilities, visit here.

Follow us on social media for the latest updates in B2B!

Image

Latest

upskilling
Upskilling Revolution: Embracing Lifelong Learning to Close the Skills Gap in Today’s Workforce
September 20, 2024

As companies face a rapidly evolving workforce, exacerbated by the COVID-19 pandemic and the growing presence of AI and automation, the traditional approach to employee education is no longer sufficient. A report by Springboard highlights that upskilling is now crucial, with 70% of corporate leaders recognizing a significant skills gap that is negatively affecting business…

Read More
The Road to the Dallas 100™ – DFW Healthcare (Anders Group, Cariloop, Focus Staff)
September 20, 2024

In this special roundtable episode of The Road to the Dallas 100, host Daniel Litwin welcomes three prominent leaders from the DFW health care space: Paul Helm, CEO of FocusStaff; Michael Walsh, cofounder of Cariloop; and Nicole Cox, cofounder of the Anders Group. Together, they explore the challenges, personal stories, and strategies behind building…

Read More
The Road to the Dallas 100™ – DFW Private Luxury Aviation (Million Air, Leviate Air Group)
September 20, 2024

In this episode of The Road to the Dallas 100, host Daniel Litwin takes listeners on a special journey, not down the road but up into the skies with a roundtable episode, aptly titled “The Runway to the Dallas 100.” Today’s show shines a spotlight on two major players in the competitive luxury private…

Read More
The Road to the Dallas 100™ – Free Range Concepts
September 19, 2024

In this episode of The Road to the Dallas 100, host Daniel Litwin welcomes Kyle Noonan and Josh Sepkowitz, cofounders of FreeRange Concepts, the innovative company behind some of DFW’s most beloved restaurant and hospitality brands, including The Rustic, Bowl & Barrel, and Mutts Canine Cantina. Known for creating memorable experiences that blend elevated…

Read More